    The main features of the TKYN61-40.5 口armored removable AC metal-enclosed switching device (hereinafter referred to as “switchgear”) are that TZN85-40.5 and VD4, VB2 type fully insulated vacuum circuit breaker and spring operating mechanism are used in the cabinet, and the cabinet body is assembled with aluminum zinc plate, improving the coordination accuracy of hand truck and cabinet body, hand car push pull out is very light, interchangeability is strong. The appearance is beautiful, the plan is complete, and the use is safe and reliable.

    This product is used in 35kV three-phase AC 50Hz power system, as a power plant, substation and industrial and mining power distribution room for receiving and distribution of electricity, with control, protection and monitoring functions.

    This product accords with: GB3906 3-35kV AC Metal-enclosed Switchgear GB / T11022 High Voltage Switchgear and Control Equipment Standard Common Technical Requirements DL / T404 AC High Voltage Switchgear Ordering Technical Requirements IEC298 Rated Voltage Above 1KV 52KV and Below AC Metal-enclosed Switchgear and Control Equipment Standard.

     xdr

    Main technical parameters

    Name

     

    Unit

    Date

    Rated voltage

     

    kV

    40.5

    Rated current

    Rated current of main busbar

    A

    630、1250、1600、2000

    Rated current of circuit breakers

    A

    630、1250、1600、2000

    Rated insulation level

    1min power frequency tolerance voltage, pole-to-pole, inter-polar / interbreak

    kV

    95/110

    Lightning impulse withstand voltage (peak), between poles, between poles / between breaks

    kV

    185/215

    Power frequency withstand voltage of auxiliary circuit and control circuit

    V/1min

    2000

    Rated frequency

    Hz

    50

    Rated short-circuit breaking current

    kA

    20、25、31.5

    Rated short-time withstand current / rated short-circuit duration

    kA/4s

    20、25、31.5

    Rated peak withstand current

    kA

    50、63、80

    Rated short-circuit closing current

    kA

    50、63、80

    Control circuit rated voltage

    V

    DC:10 220,AC:110 220

    levels of protection

    Switchgear housing

     

    IP4X

    Cubicle (when the door opens)

     

    IP2X